General Characteristics
3 Phase, 50 Hz, PF 0.8
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
ALTERNATOR SPECIFICATIONS
SIZE and WEIGHT
Control system: DSE 6120
1. Menu navigation keys
2. Power and transfer button
3. Operating status and measurement indicators with LCD
4. Error alarm LEDs
5. Generator and transmit button
6. Status LEDs
7. Operating mode selection buttons
Devices
●DSE, Model 6120, Automatic Line Fault Monitor and Generator Control Module. ●Electronic battery charger input 198-264 volts, output 27.6V 5A (24V) or 13.8 volt 5A (12V)
●Fuses for emergency stop button and control circuits.
construction and color
The devices are mounted on the sheet steel control cabinet. The plate sheet is coated with phosphate chemical and the sheet surface is corrosion resistant. An extremely durable paint finish is applied to the control panel cabinet using polyester compound powder paint and baking. Thanks to the latched and hinged control panel cover, the devices are easy to reach.
Assembly
The control panel is fixed to the generator set chassis with steel feet.
The panel is located on the right side of the generator set (when the set is fished from the alternator).
generator control unit
The DSE 6120 control module performs automatic starting and stopping of generator sets with gas and diesel engines. The module is used to monitor and display frequency, voltage, current, engine oil pressure, coolant temperature, running hours and battery voltage of the generator on the LCD screen.
In addition, the module monitors the grid voltage and frequency and controls the emergency generator and the power transmission system connected to it. If an error occurs in the generator, the generator will be automatically stopped and the corresponding error will be displayed on the LCD screen on the front of the module.
standard features
●Control by microprocessor.
●Easy to read information from the LCD screen.
●Transfer control between grid and generator power.
●Manual programming from the front panel.
●The key layout and operating system are simple.
●Remote control.
●Ability to view 50 alarms stored in memory.
●Control buttons: Stop/Zero, Manual, Auto, Test, Start, Buttons. Button to advance information on the LCD screen. Gauges
ENGINE
●Engine speed.
●Oil pressure.
●Water temperature.
●working hour.
●Battery voltage.
●Adjustable timing.
GENERATOR
●Voltage (LL, LN).
●Currents (L1-L2-L3).
●Frequency.
●Generator ready.
●The generator is on.
NETWORK
●Voltage (LL, LN).
●Frequency.
●Network ready.
●The network is activated.Protection circuits
CAUTION
●Malfunction of charge generator.
●Low/high battery voltage.
●End the malfunction.
●Low/high generator voltage.
●Low/high generator frequency.
●Low/high engine speed.
●Low oil pressure.
●High water temperature.
STOP ALARMS
●Startup error.
●Emergency stop.
●Low oil pressure.
●High water temperature.
●Low/high engine speed.
●Low/high generator frequency.
●Low/high generator voltage.
●There is no connection for the oil pressure sensor.
●There is no temperature sensor connection.
ELECTRICAL TRIP
●Generator overcurrent.
Optional features
●Possibility of pressure, temperature and percentage control with external sensor (warning, shutdown and power failure).
●Local programming and monitoring of the module via USB cable from PC (max. 6 meters).Standards
●Electrical safety/EMC compliance
●BS EN 60950 Electrical Work Equipment
●BS EN 61000-6-2 EMC exemption
●BS EN 61000-6-4 EMC Emission Standard
Electronic battery charger
●The battery charger is made with switching mode and SMD technology and has high efficiency.
●The battery is charged according to the V-I characteristic. 5 amps, 13.8 volts (12V) and 27.6 volts (24V). Input 198 - 264 volts AC.
●The device output is protected against short circuits.
●The Load Error output is available.
●Rejection of magnetic interference with RFI filter.
●Galvanically isolated inputs and outputs are jump-proof up to 4 kV.
TS ISO 8528
TS ISO 9001-2008
CE
SZUTEST
2000/14/EC
General Characteristics
Model Name | APD 43 C | ||
---|---|---|---|
Frequency (Hz) | 50 | ||
Fuel Type | Diesel | ||
Engine Made and Model | CUMMINS - 4BT3.9-G2 | ||
Alternator Made and Model | Aksa - AK 232 | ||
Control Panel Model | DSE 6120 | ||
Canopy | ACP 5 |
3 Phase, 50 Hz, PF 0.8
VOLTAGE | STANDBY RATING (ESP) | PRIME RATING (PRP) | Standby Amper | ||
---|---|---|---|---|---|
kVA | kW | kVA | kW | ||
400/231 | 43 | 34.40 | 39 | 31.20 | 62.07 |
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine | CUMMINS | ||
---|---|---|---|
Engine Model | 4BT3.9-G2 | ||
NO. OF CYLINDERS AND BUILD | 4 cylinders - in line | ||
BORE AND STROKE | mm | 102 X 120 | |
TOTAL DISPLACEMENT | L | 3,90 | |
Aspiration | Turbo Charged | ||
COMPRESSION RATIO | 18:1 | ||
RATED SPEED (RPM) | d/dk | 1500 | |
OIL CAPACITY | L | 10,9 | |
Standby Power (kW/HP) | 40/54 | ||
Prime Power | 36/48 | ||
Block Heater QTY | |||
1 | |||
Block Heater Power (Watt) | |||
500 | |||
Fuel Type | |||
Diesel | |||
Injection Type and System | |||
Direct | |||
Type of Fuel Pump | |||
BYC A | |||
Governor System | |||
Electronic | |||
Operating Voltage (Vdc) | |||
24 Vdc | |||
Battery and Capacity (Qty/Ah) | |||
2x55 | |||
Charge Alternator (A) | |||
40 | |||
Cooling Method | |||
Water Cooled | |||
Cooling Fan Air Flow (m3/min) | |||
150 | |||
Coolant Capacity (engine only / with radiator) (lt) | |||
7.2/21.2 | |||
Air Filter | |||
Dry Type | |||
Fuel Cons. Prime With %100 Load (lt/hr) | |||
9,3 | |||
Fuel Cons. Prime With %75 Load (lt/hr) | |||
7,3 | |||
Fuel Cons. Prime With %50 Load (lt/hr) | |||
5,3 |
ALTERNATOR SPECIFICATIONS
Manufacturer | Aksa | |
---|---|---|
Alternator Made and Model | AK 232 | |
Frequency (Hz) | Hz | 50 |
Power (kVA) | kVA | 40 |
DESIGN | Brushless | |
VOLTAGE | V | 400 |
Phase | 3 | |
A.V.R. | AS460 | |
Voltage Regulation | (+/-) | 1,5% |
Insulation System | H | |
Protection | IP22 | |
Rated Power Factor | 0.8 | |
WEIGHT COMP. GENERATOR (Kg) | 226 | |
COOLING AIR (m³/min) | m3 | 9 |
SIZE and WEIGHT
Open Type | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
---|---|---|---|---|---|
900 | 2015 | 950 | 1411 | 180 | |
CANOPY | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
ACP 5 |
1120 | 2282 | 1008 | 1532 | 180 |
Control system: DSE 6120
1. Menu navigation keys
2. Power and transfer button
3. Operating status and measurement indicators with LCD
4. Error alarm LEDs
5. Generator and transmit button
6. Status LEDs
7. Operating mode selection buttons
Devices
●DSE, Model 6120, Automatic Line Fault Monitor and Generator Control Module. ●Electronic battery charger input 198-264 volts, output 27.6V 5A (24V) or 13.8 volt 5A (12V)
●Fuses for emergency stop button and control circuits.
construction and color
The devices are mounted on the sheet steel control cabinet. The plate sheet is coated with phosphate chemical and the sheet surface is corrosion resistant. An extremely durable paint finish is applied to the control panel cabinet using polyester compound powder paint and baking. Thanks to the latched and hinged control panel cover, the devices are easy to reach.
Assembly
The control panel is fixed to the generator set chassis with steel feet.
The panel is located on the right side of the generator set (when the set is fished from the alternator).
generator control unit
The DSE 6120 control module performs automatic starting and stopping of generator sets with gas and diesel engines. The module is used to monitor and display frequency, voltage, current, engine oil pressure, coolant temperature, running hours and battery voltage of the generator on the LCD screen.
In addition, the module monitors the grid voltage and frequency and controls the emergency generator and the power transmission system connected to it. If an error occurs in the generator, the generator will be automatically stopped and the corresponding error will be displayed on the LCD screen on the front of the module.
standard features
●Control by microprocessor.
●Easy to read information from the LCD screen.
●Transfer control between grid and generator power.
●Manual programming from the front panel.
●The key layout and operating system are simple.
●Remote control.
●Ability to view 50 alarms stored in memory.
●Control buttons: Stop/Zero, Manual, Auto, Test, Start, Buttons. Button to advance information on the LCD screen. Gauges
ENGINE
●Engine speed.
●Oil pressure.
●Water temperature.
●working hour.
●Battery voltage.
●Adjustable timing.
GENERATOR
●Voltage (LL, LN).
●Currents (L1-L2-L3).
●Frequency.
●Generator ready.
●The generator is on.
NETWORK
●Voltage (LL, LN).
●Frequency.
●Network ready.
●The network is activated.Protection circuits
CAUTION
●Malfunction of charge generator.
●Low/high battery voltage.
●End the malfunction.
●Low/high generator voltage.
●Low/high generator frequency.
●Low/high engine speed.
●Low oil pressure.
●High water temperature.
STOP ALARMS
●Startup error.
●Emergency stop.
●Low oil pressure.
●High water temperature.
●Low/high engine speed.
●Low/high generator frequency.
●Low/high generator voltage.
●There is no connection for the oil pressure sensor.
●There is no temperature sensor connection.
ELECTRICAL TRIP
●Generator overcurrent.
Optional features
●Possibility of pressure, temperature and percentage control with external sensor (warning, shutdown and power failure).
●Local programming and monitoring of the module via USB cable from PC (max. 6 meters).Standards
●Electrical safety/EMC compliance
●BS EN 60950 Electrical Work Equipment
●BS EN 61000-6-2 EMC exemption
●BS EN 61000-6-4 EMC Emission Standard
Electronic battery charger
●The battery charger is made with switching mode and SMD technology and has high efficiency.
●The battery is charged according to the V-I characteristic. 5 amps, 13.8 volts (12V) and 27.6 volts (24V). Input 198 - 264 volts AC.
●The device output is protected against short circuits.
●The Load Error output is available.
●Rejection of magnetic interference with RFI filter.
●Galvanically isolated inputs and outputs are jump-proof up to 4 kV.